Stracau 14GL0F01 Brass Solenoid Valve, Normally Closed
14GL0F01 is a Stracau normally closed brass solenoid valve, female G 3/4"-1", 10 bar, -5 to +90 °C; also in 24 V AC and 24 V DC versions.
- Brand Stracau
- Origin France
- Type Normally closed direct-control 2/2 solenoid valve, 10 bar
- Size 3/4", 1"
- Genuine products
- Full CO/CQ
- VAT invoice
- Quote within 24 working hours
PRODUCT DESCRIPTION
Stracau 14GL0F01 Brass Solenoid Valve, Normally Closed
14GL0F01 is a Stracau (France) brass direct-control 2/2 solenoid valve, normally closed, female G 3/4″ and 1″. CW617N brass body, EPDM KTW diaphragm, maximum working pressure 10 bar, temperature -5 to +90 °C, coil voltage 230 V AC (14GL0F01), 24 V AC (14GL0F02) or 24 V DC (14GL0F03).
14GL0F01 specifications
- Type: Normally closed direct-control 2/2 solenoid valve, 10 bar
- Size: 3/4″, 1″
- Connection: Female G thread (ISO 228)
- Body and cover: Brass CW617N (EN 1503-4)
- Core and internal parts: Stainless steel
- Diaphragm: EPDM KTW
- Max. working pressure: 10 bar
- Working temperature: -5 to +90 °C
- Differential pressure: Operates without differential pressure; max. 4 bar (AC), 2 bar (DC)
- Operating time: 20 to 60 ms
- Coil: Coil B12, class H, 100 % duty, DIN 43650 (T30) connector, IP65
- Voltages: 14GL0F01: 230 V AC 50 Hz; 14GL0F02: 24 V AC 50 Hz; 14GL0F03: 24 V DC
- Coil power: AC: 18 VA hold, 47 VA inrush; DC: 21 W
- Approval: A.C.S. agreement 10 ACC LY 169
- Mounting: Horizontal, coil on top; follow the arrow on the body
Dimensions by thread size
From the Stracau 14GL0F01 datasheet and the CAD document; coil B12.
| Thread size | Bore (mm) | Kv (m3/h) | Length A (mm) |
|---|---|---|---|
| 3/4″ | 20 | 5.5 | 87 |
| 1″ | 25 | 7.5 | 100 |
Applications
Automatic sectioning of common fluid networks: water, air, neutral gases, etc. (per the Stracau datasheet).
TECHNICAL SPECIFICATIONS
Specifications of Stracau 14GL0F01 Brass Solenoid Valve, Normally Closed
| PARAMETER | VALUE |
|---|---|
| Model | 14GL0F01 / 14GL0F02 / 14GL0F03 |
| Brand | Stracau |
| Origin | France |
| Type | Normally closed direct-control 2/2 solenoid valve, 10 bar |
| Size | 3/4", 1" |
| Connection | Female G thread (ISO 228) |
| Body and cover | Brass CW617N (EN 1503-4) |
| Core and internal parts | Stainless steel |
| Diaphragm | EPDM KTW |
| Max. working pressure | 10 bar |
| Working temperature | -5 to +90 °C |
| Differential pressure | Operates without differential pressure; max. 4 bar (AC), 2 bar (DC) |
| Operating time | 20 to 60 ms |
| Coil | Coil B12, class H, 100 % duty, DIN 43650 (T30) connector, IP65 |
| Voltages | 14GL0F01: 230 V AC 50 Hz; 14GL0F02: 24 V AC 50 Hz; 14GL0F03: 24 V DC |
| Coil power | AC: 18 VA hold, 47 VA inrush; DC: 21 W |
| Approval | A.C.S. agreement 10 ACC LY 169 |
| Mounting | Horizontal, coil on top; follow the arrow on the body |
Specifications may vary with the ordered configuration. Contact a CAD engineer for sizing to your actual operating conditions.
FAQ
Frequently asked questions about 14GL0F01 / 14GL0F02 / 14GL0F03
How do 14GL0F01, 14GL0F02 and 14GL0F03 differ?
Only the coil voltage: 14GL0F01 is 230 V AC 50 Hz, 14GL0F02 is 24 V AC 50 Hz, 14GL0F03 is 24 V DC. Same valve body, same 3/4" and 1" sizes.
Does 14GL0F01 need a differential pressure to work?
No. The datasheet says it operates without differential pressure; maximum differential is 4 bar with an AC coil and 2 bar with a DC coil.
How do I get a quote for 14GL0F01?