Honeywell FSL100 UV, UV/IR and IR3 Flame Detector
100% GENUINE
View larger
Honeywell FSL100 UV, UV/IR and IR3 Flame Detector

Honeywell FSL100 UV, UV/IR and IR3 Flame Detector

PRODUCT CODE
FSL100
BRAND
Honeywell

FSL100 is a Honeywell flame detector range with UV, UV/IR and IR3 versions, 25-35 m range, 4-20 mA and relay outputs, 10-28 VDC supply, an IP65 GRP housing and ATEX zone 2/22.

  • Brand Honeywell
  • Product type UV, UV/IR or triple IR (IR3) flame detector
  • Range 35 m (110 ft) for IR3; 25 m (80 ft) for UV and UV/IR; alarming within 10 seconds to a 0.1 m2 (1 ft2) n-heptane fire
  • Cone of vision 90° minimum horizontal and vertical
REQUEST A QUOTE DOWNLOAD DATASHEET (PDF)
  • Genuine products
  • Full CO/CQ
  • VAT invoice
  • Quote within 24 working hours

PRODUCT DESCRIPTION

Honeywell FSL100 UV, UV/IR and IR3 Flame Detector

FSL100 is Honeywell’s compact range of flame detectors in three versions: UV, UV/IR and triple IR (IR3). Range 25 m (UV, UV/IR) or 35 m (IR3), cone of vision of at least 90°, 4-20 mA and relay outputs as standard, 10-28 VDC supply. UV-resistant GRP housing, IP65, for indoor and outdoor use, ATEX zone 2/22, with EN54-10 and FM3260 approvals depending on the version.

How do FSL100-UV, FSL100-UVIR and FSL100-IR3 differ?

The three FSL100 versions differ in sensing technology, range and the fires they suit. FSL100-UV: UV sensor, 25 m range; suited to cold storage, laboratories, fume hoods and hydrogen storage areas, and to materials burning at low temperatures such as sulphur. FSL100-UVIR: UV/IR, 25 m range; analyses flame flicker frequency to reduce false alarms and detects a wide range of hydrocarbon and non-hydrocarbon fires. FSL100-IR3: triple IR, 35 m range; suited to liquid hydrocarbon and dirty fires or fires with a lot of smoke, and less affected by window contamination.

FSL100 specifications

  • Brand: Honeywell
  • Product type: UV, UV/IR or triple IR (IR3) flame detector
  • Range: 35 m (110 ft) for IR3; 25 m (80 ft) for UV and UV/IR; alarming within 10 seconds to a 0.1 m2 (1 ft2) n-heptane fire
  • Cone of vision: 90° minimum horizontal and vertical
  • Power: 10-28 VDC (12-24 VDC nominal); 25 mA at 24 VDC normal; about 75 mA in alarm
  • Current output: 4-20 mA (stepped, sinking, non-isolated): 0 mA power / microprocessor fault; 2 mA optical fault; 4 mA normal operation; above 20 mA alarm
  • Relay output: Alarm relay (de-energised in normal operation) and fault relay (energised in normal operation, no fault), SPDT, 30 VDC 2 A, 60 W max
  • Timing: Start-up under 10 seconds; alarm response time 8 to 30 seconds
  • Local LEDs: Continuous green: normal; continuous yellow: fault; flashing yellow: fault and guide to repeat self-test; continuous red: alarm
  • Self-test: Automatic sensor self-test and manual self-test; remote manual self-test option
  • Housing: Glass reinforced polyester (GRP), non-incendive, UV resistant, self-extinguishing V-0 (UL-94); red or white
  • Dimensions / weight: 125 x 80 x 57 mm; 465 g
  • Ingress protection: IP65
  • Operating temperature: -40°C to +70°C; ATEX and FM 3611: -25°C to +70°C
  • Cable gland and terminals: M20 cable entry supplied with gland for cable diameter 5.5-13 mm; terminals for 0.5-1.5 mm2 (20-15 AWG) wire
  • Connections to: Fire control panels using end-of-line (EOL) and alarm resistors; devices operated by relay outputs; PLCs with 4-20 mA inputs
  • Certifications: EN54-10: UV and UV/IR Class 2, IR3 Class 1 (pending); ATEX zone 2/22; FM3260; FM3611 non-incendive (pending)
  • Accessories: FS1000-SM21: swivel mount (ordered separately); FSL100-TL: test lamp including universal charger and carrying case, non Ex

How does FSL100 differ from FS24X Plus and FS20X?

FSL100 differs from FS24X Plus and FS20X in size, housing and operating range. FSL100: 125 x 80 x 57 mm GRP housing, IP65, 10-28 VDC supply, -40°C to +70°C operating temperature, ATEX zone 2/22, 25-35 m range. FS24X Plus and FS20X: aluminium or stainless steel enclosures rated IP66 or better, 18-32 VDC supply, range up to 60 m, ATEX / IECEx Ex db IIC.

Order codes

The swivel mount (FS1000-SM21) is ordered separately.

Order code Description
FSL100-UV UV flame detector. Suitable for ATEX zone 2/22; FM 3611 Class 1, 2 & 3 Div 2; EN54-10 (HIGH sensitivity), FM3260 approval, red housing
FSL100-UV-W UV flame detector. Suitable for ATEX zone 2/22; FM 3611 Class 1, 2 & 3 Div 2; EN54-10 (HIGH sensitivity), FM3260 approval, white housing
FSL100-UVIR UV/IR flame detector. Suitable for ATEX zone 2/22; FM 3611 Class 1, 2 & 3 Div 2; EN54-10 (HIGH sensitivity), FM3260 approval, red housing
FSL100-UVIR-W UV/IR flame detector. Suitable for ATEX zone 2/22; FM 3611 Class 1, 2 & 3 Div 2; EN54-10 (HIGH sensitivity), FM3260 approval, white housing
FSL100-IR3 Triple IR flame detector. Suitable for ATEX zone 2/22; FM 3611 Class 1, 2 & 3 Div 2; EN54-10 (HIGH sensitivity), FM3260 approval, red housing
FSL100-IR3-W Triple IR flame detector. Suitable for ATEX zone 2/22; FM 3611 Class 1, 2 & 3 Div 2; EN54-10 (HIGH sensitivity), FM3260 approval, white housing

Applications

The datasheet lists FSL100 applications by version (UV, UV/IR or IR3): aircraft hangars, atriums, battery storage rooms / data communication rooms, biogas, car, bus, tram and train parking, clean rooms (semiconductor, pharmaceutical, hospital operating rooms), CNG filling for buses, cold storage, diesel engine rooms, electric power transformers, engine test cells / rooms, fume hoods, gas cabinets, chemical heating rooms, indoor chemical, fuel and solvent storage, indoor hydrocarbon or hydrogen storage and processing, laboratories, truck, rail and marine loading and unloading terminals, monitoring of machinery, oil and gas pipelines and pumping stations, paint spray booths, recycling and waste processing plants.

TECHNICAL SPECIFICATIONS

Specifications of Honeywell FSL100 UV, UV/IR and IR3 Flame Detector

PARAMETER VALUE
Model FSL100
Brand Honeywell
Product type UV, UV/IR or triple IR (IR3) flame detector
Range 35 m (110 ft) for IR3; 25 m (80 ft) for UV and UV/IR; alarming within 10 seconds to a 0.1 m2 (1 ft2) n-heptane fire
Cone of vision 90° minimum horizontal and vertical
Power 10-28 VDC (12-24 VDC nominal); 25 mA at 24 VDC normal; about 75 mA in alarm
Current output 4-20 mA (stepped, sinking, non-isolated): 0 mA power / microprocessor fault; 2 mA optical fault; 4 mA normal operation; above 20 mA alarm
Relay output Alarm relay (de-energised in normal operation) and fault relay (energised in normal operation, no fault), SPDT, 30 VDC 2 A, 60 W max
Timing Start-up under 10 seconds; alarm response time 8 to 30 seconds
Local LEDs Continuous green: normal; continuous yellow: fault; flashing yellow: fault and guide to repeat self-test; continuous red: alarm
Self-test Automatic sensor self-test and manual self-test; remote manual self-test option
Housing Glass reinforced polyester (GRP), non-incendive, UV resistant, self-extinguishing V-0 (UL-94); red or white
Dimensions / weight 125 x 80 x 57 mm; 465 g
Ingress protection IP65
Operating temperature -40°C to +70°C; ATEX and FM 3611: -25°C to +70°C
Cable gland and terminals M20 cable entry supplied with gland for cable diameter 5.5-13 mm; terminals for 0.5-1.5 mm2 (20-15 AWG) wire
Connections to Fire control panels using end-of-line (EOL) and alarm resistors; devices operated by relay outputs; PLCs with 4-20 mA inputs
Certifications EN54-10: UV and UV/IR Class 2, IR3 Class 1 (pending); ATEX zone 2/22; FM3260; FM3611 non-incendive (pending)
Accessories FS1000-SM21: swivel mount (ordered separately); FSL100-TL: test lamp including universal charger and carrying case, non Ex

Specifications may vary with the ordered configuration. Contact a CAD engineer for sizing to your actual operating conditions.

FAQ

Frequently asked questions about FSL100

How do FSL100-UV, FSL100-UVIR and FSL100-IR3 differ?

FSL100-UV uses a UV sensor with 25 m range and suits cold storage, fume hoods and hydrogen storage areas. FSL100-UVIR is UV/IR with 25 m range and analyses flicker frequency to reduce false alarms. FSL100-IR3 is triple IR with 35 m range and suits liquid hydrocarbon fires and dirty or smoky fires.

What outputs and supply does FSL100 have?

A 10-28 VDC supply (12-24 VDC nominal). Standard outputs are 4-20 mA (stepped, sinking, non-isolated) plus an alarm relay and a fault relay (SPDT, 30 VDC 2 A).

Which certifications does FSL100 have?

ATEX zone 2/22 and FM3260 for all three versions; EN54-10 Class 2 for UV and UV/IR and Class 1 for IR3 (pending); FM3611 non-incendive (pending). IP65 GRP housing.

Used this product? Write a review

Your rating

20 to 1500 characters, no links.

CAD uses your name, company and text only to publish your review once approved. Your email is for CAD to check only; it is never shown or used for anything else.

Quote