FS24X Plus is a Honeywell triple IR (IR3) flame detector with a range up to 60 m, 4-20 mA / HART / Modbus outputs, ATEX, IECEx, SIL 2 and an IP66/67 enclosure.

  • Brand Honeywell
  • Product type Triple IR (IR3) flame detector for hydrocarbon and hydrogen fires
  • Field of view 90° cone of vision; 120° cone (50% on-axis range)
  • Sensitivity / range Low 15 m (50 ft), medium 30 m (100 ft), high 45 m (150 ft), very high 60 m (200 ft) to a 0.1 m2 (1 ft2) n-heptane fire; configured with Flame Manager
REQUEST A QUOTE DOWNLOAD DATASHEET (PDF)
  • Genuine products
  • Full CO/CQ
  • VAT invoice
  • Quote within 24 working hours

PRODUCT DESCRIPTION

Honeywell FS24X Plus Triple IR (IR3) Flame Detector

FS24X Plus is a Honeywell triple IR (IR3) flame detector that responds to hydrocarbon and hydrogen fires over a wide field of view, with a detection range up to 60 m to a 0.1 m2 n-heptane fire. Solid-state, wide-band sensors allow detection through rain, fog and smoke. 4-20 mA, relay, HART and Modbus outputs; ATEX, IECEx, cFMus, SIL 2, FM3260 and EN54-10 certifications; IP66/67 enclosure.

How does FS24X Plus differ from FS20X and FSL100?

FS24X Plus differs from FS20X and FSL100 in sensing technology, range and housing. FS24X Plus: triple IR (IR3), 15-60 m range, typically responds in 5 seconds, aluminium or 316 stainless steel IP66/67 enclosure, ATEX / IECEx Ex db IIC T5, SIL 2, with HART and Modbus. FS20X: multi-spectrum UV / dual IR / visible (VIS), 15-60 m range, 3-5 second response at 30 m, IP66 enclosure, ATEX / IECEx Ex db IIC, HART as an optional module. FSL100: three versions, UV, UV/IR or IR3, in an IP65 GRP housing, 25 m (UV, UV/IR) or 35 m (IR3) range, 10-28 VDC supply, ATEX zone 2/22.

FS24X Plus specifications

  • Brand: Honeywell
  • Product type: Triple IR (IR3) flame detector for hydrocarbon and hydrogen fires
  • Field of view: 90° cone of vision; 120° cone (50% on-axis range)
  • Sensitivity / range: Low 15 m (50 ft), medium 30 m (100 ft), high 45 m (150 ft), very high 60 m (200 ft) to a 0.1 m2 (1 ft2) n-heptane fire; configured with Flame Manager
  • Response time: Typically 5 seconds, 10 seconds maximum (FM witnessed); 3-5 seconds possible under specific conditions
  • Operating voltage: 24 VDC nominal (18 to 32 VDC), regulated
  • Power consumption: 1.8 W (nominal); 2.4 W (alarm); 12 W maximum with heater at 100% duty cycle
  • Output relays: Alarm, fault and auxiliary: SPDT (NO/NC), de-energised / energised, latching / non-latching; rated 2 A at 32 VDC
  • Analog output: 4-20 mA: source, sink or isolated
  • Digital communications: RS-485: Modbus and FP2; USB: FP2; HART with handheld communicator or hardwired
  • Operating temperature: -55°C to +75°C (North America: -50°C to +75°C); storage -55°C to +85°C (North America: -50°C to +85°C)
  • Humidity range: 0 to 99% relative humidity or 100% condensing humidity for short periods
  • Cable / conduit entries: 2 x M25 or 2 x ¾” NPT
  • Enclosure material: Low-copper aluminium with marine-grade paint or 316 stainless steel
  • Enclosure type: IP66 / IP67 (Type 4X)
  • Tested fuels: n-Heptane, IPA, methane, butane, propane, ethanol, methanol, hydrogen, diesel, kerosene, JP-4
  • Hazardous location certifications: ATEX: II 2 G Ex db IIC T5 Gb; II 2 D Ex tb IIIC T135°C Db IP66/67. IECEx: Ex db IIC T5 Gb; Ex tb IIIC T135°C Db IP66/67. cFMus: Class I Div 1 Groups A, B, C, D; Class II/III Div 1 Groups E, F, G, NEMA 4X. INMETRO
  • Performance and safety certifications: FM3260; EN54-10: Class 1 (medium, high, very high sensitivity), Class 2 (low sensitivity); IEC 61508 SIL 2 certified by TUV Sud
  • Pending: CU-TR, CCC and marine type approvals (ABS, Lloyds, BV, DNV): marked “pending” in the datasheet

Main features

A high-visibility LED halo ring shows status from a distance: green (normal), yellow (fault / warning), red (alarm). The SM4 mount is included as standard (a marine SM4-M mount is available). Set-up is by the Flame Manager PC app or HART; Flame Manager includes post-event analysis with the FirePic tool. It has window-clarity diagnostics, a test lamp for testing at a distance and an electro-optics module that can be swapped in the field. The datasheet describes the unit as calibration free.

Order codes

FS24XP- code structure per the datasheet: material (A aluminium, S stainless steel), entries (M = M25, N = ¾” NPT), approvals G (global), X reserved, installation (X standard mount + sunshade, M marine mount + sunshade).

Order code Description
FS24XP-ANGXX FS24X Plus – 3IR – aluminium (AL) – ¾” NPT cable entries, kit includes mount and sunshade
FS24XP-AMGXX FS24X Plus – 3IR – aluminium (AL) – M25 cable entries, kit includes mount and sunshade
FS24XP-SNGXX FS24X Plus – 3IR – stainless steel (SS) – ¾” NPT cable entries, kit includes mount and sunshade
FS24XP-SMGXX FS24X Plus – 3IR – stainless steel (SS) – M25 cable entries, kit includes mount and sunshade
FS24XP-ANGXM FS24X Plus – 3IR – aluminium (AL) – ¾” NPT cable entries, kit includes marine mount and sunshade
FS24XP-AMGXM FS24X Plus – 3IR – aluminium (AL) – M25 cable entries, kit includes marine mount and sunshade
FS24XP-SNGXM FS24X Plus – 3IR – stainless steel (SS) – ¾” NPT cable entries, kit includes marine mount and sunshade
FS24XP-SMGXM FS24X Plus – 3IR – stainless steel (SS) – M25 cable entries, kit includes marine mount and sunshade

Applications

Flame detection in demanding industrial environments with hydrocarbon fires (heptane, IPA, methane, butane, propane, ethanol, methanol, diesel, kerosene, JP-4) or hydrogen fires. It operates from -55°C to +75°C with an IP66/67 enclosure, suited to outdoor mounting.

TECHNICAL SPECIFICATIONS

Specifications of Honeywell FS24X Plus

PARAMETER VALUE
Model FS24X Plus
Brand Honeywell
Product type Triple IR (IR3) flame detector for hydrocarbon and hydrogen fires
Field of view 90° cone of vision; 120° cone (50% on-axis range)
Sensitivity / range Low 15 m (50 ft), medium 30 m (100 ft), high 45 m (150 ft), very high 60 m (200 ft) to a 0.1 m2 (1 ft2) n-heptane fire; configured with Flame Manager
Response time Typically 5 seconds, 10 seconds maximum (FM witnessed); 3-5 seconds possible under specific conditions
Operating voltage 24 VDC nominal (18 to 32 VDC), regulated
Power consumption 1.8 W (nominal); 2.4 W (alarm); 12 W maximum with heater at 100% duty cycle
Output relays Alarm, fault and auxiliary: SPDT (NO/NC), de-energised / energised, latching / non-latching; rated 2 A at 32 VDC
Analog output 4-20 mA: source, sink or isolated
Digital communications RS-485: Modbus and FP2; USB: FP2; HART with handheld communicator or hardwired
Operating temperature -55°C to +75°C (North America: -50°C to +75°C); storage -55°C to +85°C (North America: -50°C to +85°C)
Humidity range 0 to 99% relative humidity or 100% condensing humidity for short periods
Cable / conduit entries 2 x M25 or 2 x ¾" NPT
Enclosure material Low-copper aluminium with marine-grade paint or 316 stainless steel
Enclosure type IP66 / IP67 (Type 4X)
Tested fuels n-Heptane, IPA, methane, butane, propane, ethanol, methanol, hydrogen, diesel, kerosene, JP-4
Hazardous location certifications ATEX: II 2 G Ex db IIC T5 Gb; II 2 D Ex tb IIIC T135°C Db IP66/67. IECEx: Ex db IIC T5 Gb; Ex tb IIIC T135°C Db IP66/67. cFMus: Class I Div 1 Groups A, B, C, D; Class II/III Div 1 Groups E, F, G, NEMA 4X. INMETRO
Performance and safety certifications FM3260; EN54-10: Class 1 (medium, high, very high sensitivity), Class 2 (low sensitivity); IEC 61508 SIL 2 certified by TUV Sud
Pending CU-TR, CCC and marine type approvals (ABS, Lloyds, BV, DNV): marked "pending" in the datasheet

Specifications may vary with the ordered configuration. Contact a CAD engineer for sizing to your actual operating conditions.

FAQ

Frequently asked questions about CAD-SF-410

How does FS24X Plus differ from FS20X and FSL100?

FS24X Plus uses triple IR (IR3), has a 15-60 m range, an IP66/67 enclosure, ATEX / IECEx Ex db IIC T5, SIL 2, and offers HART and Modbus. FS20X is a multi-spectrum UV / dual IR / visible detector with an IP66 enclosure. FSL100 comes as UV, UV/IR or IR3 in an IP65 GRP housing, with 25 m (UV, UV/IR) or 35 m (IR3) range and ATEX zone 2/22.

How far does FS24X Plus detect and how fast does it respond?

The range is configurable: 15 m, 30 m, 45 m or 60 m to a 0.1 m2 n-heptane fire. Response time is typically 5 seconds and 10 seconds at most (FM witnessed).

What outputs and certifications does FS24X Plus have?

4-20 mA output (source, sink or isolated), alarm / fault / auxiliary relays, RS-485 Modbus and FP2, USB FP2 and HART. Certifications: ATEX, IECEx, cFMus, INMETRO, FM3260, EN54-10 and IEC 61508 SIL 2.

Used this product? Write a review

Your rating

20 to 1500 characters, no links.

CAD uses your name, company and text only to publish your review once approved. Your email is for CAD to check only; it is never shown or used for anything else.

Quote