Honeywell Zareba Sensepoint Pro Fixed Gas Detector
Sensepoint Pro is a Honeywell Zareba 3-wire 4-20 mA fixed gas detector with 2 alarm relays for flammable, toxic and oxygen gases, remote-control configuration, IP65, ATEX/UL.
- Brand Honeywell (Zareba range)
- Type 3-wire 4-20 mA fixed point gas detector with built-in alarm relays, transmitter with local display, configured with an intrinsically safe remote control
- Gases detected Flammable, oxygen, carbon monoxide, hydrogen sulfide, hydrogen (see range table)
- Sensor technology Surecell electrochemical sensors (toxic and oxygen); poison-resistant catalytic bead (flammable); typical 2 to 5 years operational life; plug-in replacement
- Genuine products
- Full CO/CQ
- VAT invoice
- Quote within 24 working hours
PRODUCT DESCRIPTION
Honeywell Zareba Sensepoint Pro Fixed Gas Detector
Sensepoint Pro (Honeywell Zareba range) is a 3-wire 4-20 mA fixed point gas detector with two built-in alarm relays for flammable, toxic and oxygen gas hazards in potentially explosive atmospheres, indoors and outdoors. A backlit LCD shows readings on site; users adjust range, calibration, relays and alarm set points with an intrinsically safe remote control without opening the unit. IP65 as standard.
How to choose a Sensepoint Pro code
The codes below differ in gas type and range. The Honeywell datasheet (12/2005) lists flammable, oxygen, carbon monoxide, hydrogen sulfide and hydrogen; the Cl2, SO2, NO2 and NH3 codes in the table come from CAD’s part-number list.
Measuring ranges per datasheet
| Gas | Measuring range | Operating temperature |
|---|---|---|
| Flammable (F) | 0-100 % LEL (standard range) | -20°C to 50°C |
| Oxygen (O) | 0-25 % VOL | -15°C to 40°C |
| Carbon Monoxide (C) | 0-200 ppm or 0-500 ppm | -20°C to 50°C |
| Hydrogen Sulfide (H) | 0-50 ppm, 0-20 ppm or 0-100 ppm | -20°C to 50°C |
| Hydrogen (G) | 0-1000 ppm | -5°C to 40°C |
Sensepoint Pro specifications
- Type: 3-wire 4-20 mA fixed point gas detector with built-in alarm relays, transmitter with local display, configured with an intrinsically safe remote control
- Gases detected: Flammable, oxygen, carbon monoxide, hydrogen sulfide, hydrogen (see range table)
- Sensor technology: Surecell electrochemical sensors (toxic and oxygen); poison-resistant catalytic bead (flammable); typical 2 to 5 years operational life; plug-in replacement
- Supply: 3-wire connection, 12 to 30 Vdc, common 0 Vdc; maximum operating current 300 mA (flammable), 150 mA (toxic and oxygen); maximum peak inrush current 600 mA
- Signal: 4-20 mA (source): 22 mA maximum over range, 4-20 mA normal operation, 2 mA or 4 mA output inhibited (2 mA or 17.4 mA for oxygen), 0 mA fault
- Alarm relays: 2 x 3 A @ 240 Vac alarm relays; user configurable alarm trip point, normally energized / de-energized operation; link selectable output as NO or NC
- Connection: 7 screw terminals for 0.5 to 2.5 mm2 (20 to 14 AWG) wire; 3/4″ NPT entry with M20 adaptor included
- Material: Main body powder coated aluminum (ADC12); sensor 316 stainless steel; weatherproof cap aluminum with 316 stainless steel mesh
- Weight: 1450 g
- Ingress protection: IP65 (EN 60529:1992)
- Environment: Humidity continuous 20 to 90 %RH, intermittent 10 to 99 %RH (non-condensing); pressure 90 to 110 kPa; storage -40°C to +50°C
- Certification (per datasheet): ATEX: Ex II 2G EEx d IIC T4 (Tamb -20°C to +50°C); UL: Class 1, Div 1, Groups B, C, D. ZHC1 remote control: ATEX Ex II 2G EEx ib IIC T4; UL Class 1, Div 1, Groups A, B, C, D
- Applicable standards: North America: UL1203; Europe: CE, ATEX, EMC (EN50270)
- Standard supply: IS remote control, 3/4″ NPT entry, 3/4″ NPT to M20 adaptor, wall mounting bracket, pole mounting bracket, weatherproof cap, Allen keys, instruction manual
- Optional accessories: SPPPCC collecting cone; SPPPCAL flow adaptor; SPPPDM duct mounting kit
Order codes
| Order code | Description |
|---|---|
| SPSTAXF1 | 0-100%LEL Methane |
| SPSTAXO2 | 0-25%VOL Oxygen |
| SPSTAXC1 | 0-200ppm Carbon Monoxide |
| SPSTAXC2 | 0-500ppm Carbon Monoxide |
| SPSTAXH1 | 0-50ppm Hydrogen Sulphide |
| SPSTAXH2 | 0-20ppm Hydrogen Sulphide |
| SPSTAXH3 | 0-100ppm Hydrogen Sulphide |
| SPSTAXG1 | 0-1,000ppm Hydrogen |
| SPSTAXL1 | 0-5ppm Chlorine |
| SPSTAXL2 | 0-15ppm Chlorine |
| SPSTAXS1 | 0-15ppm Sulphur Dioxide |
| SPSTAXS2 | 0-50ppm Sulphur Dioxide |
| SPSTAXN1 | 0-10ppm Nitrogen Dioxide |
| SPSTAXA1 | 0-50ppm Ammonia |
| SPSTAXA2 | 0-1000ppm Ammonia |
Applications
The Honeywell datasheet describes the detector for flammable, toxic and oxygen gas hazards in potentially explosive atmospheres, indoors or outdoors; mounted on a wall or round pole with the bracket supplied, with conduit or steel wire armored cable. Oxygen versions must only be used to detect oxygen depletion in air. The datasheet’s “Global Certifications” section carries a “Pending” note, so contact Honeywell for the latest approvals.
TECHNICAL SPECIFICATIONS
Specifications of Honeywell Zareba Sensepoint Pro Fixed Gas Detector
| PARAMETER | VALUE |
|---|---|
| Model | Sensepoint Pro |
| Brand | Honeywell (Zareba range) |
| Type | 3-wire 4-20 mA fixed point gas detector with built-in alarm relays, transmitter with local display, configured with an intrinsically safe remote control |
| Gases detected | Flammable, oxygen, carbon monoxide, hydrogen sulfide, hydrogen (see range table) |
| Sensor technology | Surecell electrochemical sensors (toxic and oxygen); poison-resistant catalytic bead (flammable); typical 2 to 5 years operational life; plug-in replacement |
| Supply | 3-wire connection, 12 to 30 Vdc, common 0 Vdc; maximum operating current 300 mA (flammable), 150 mA (toxic and oxygen); maximum peak inrush current 600 mA |
| Signal | 4-20 mA (source): 22 mA maximum over range, 4-20 mA normal operation, 2 mA or 4 mA output inhibited (2 mA or 17.4 mA for oxygen), 0 mA fault |
| Alarm relays | 2 x 3 A @ 240 Vac alarm relays; user configurable alarm trip point, normally energized / de-energized operation; link selectable output as NO or NC |
| Connection | 7 screw terminals for 0.5 to 2.5 mm2 (20 to 14 AWG) wire; 3/4" NPT entry with M20 adaptor included |
| Material | Main body powder coated aluminum (ADC12); sensor 316 stainless steel; weatherproof cap aluminum with 316 stainless steel mesh |
| Weight | 1450 g |
| Ingress protection | IP65 (EN 60529:1992) |
| Environment | Humidity continuous 20 to 90 %RH, intermittent 10 to 99 %RH (non-condensing); pressure 90 to 110 kPa; storage -40°C to +50°C |
| Certification (per datasheet) | ATEX: Ex II 2G EEx d IIC T4 (Tamb -20°C to +50°C); UL: Class 1, Div 1, Groups B, C, D. ZHC1 remote control: ATEX Ex II 2G EEx ib IIC T4; UL Class 1, Div 1, Groups A, B, C, D |
| Applicable standards | North America: UL1203; Europe: CE, ATEX, EMC (EN50270) |
| Standard supply | IS remote control, 3/4" NPT entry, 3/4" NPT to M20 adaptor, wall mounting bracket, pole mounting bracket, weatherproof cap, Allen keys, instruction manual |
| Optional accessories | SPPPCC collecting cone; SPPPCAL flow adaptor; SPPPDM duct mounting kit |
Specifications may vary with the ordered configuration. Contact a CAD engineer for sizing to your actual operating conditions.
FAQ
Frequently asked questions about Sensepoint Pro
Which gases does the Sensepoint Pro measure?
Per the datasheet: flammable 0-100 %LEL, oxygen 0-25 %VOL, carbon monoxide 0-200 or 0-500 ppm, hydrogen sulfide 0-50, 0-20 or 0-100 ppm, hydrogen 0-1000 ppm. CAD's part-number list also has chlorine, sulphur dioxide, nitrogen dioxide and ammonia.
What outputs does the Sensepoint Pro have and how is it configured?
3-wire 4-20 mA (source) output and two 3 A @ 240 Vac alarm relays. Range, calibration, relays and alarm set points are set with an intrinsically safe IR remote control; outputs are automatically inhibited during adjustment.
What ingress protection and certification does the Sensepoint Pro have?
IP65 as standard. The datasheet lists ATEX Ex II 2G EEx d IIC T4 and UL Class 1 Div 1 Groups B, C, D, with UL1203, CE, ATEX and EMC EN50270 standards.