Honeywell EC7823A1004 Burner Controller
The Honeywell EC7823A1004 is a microprocessor-based 7800 SERIES flame detector relay, 220-240 Vac, used with a Q7800 subbase and a plug-in flame signal amplifier, with a flame failure response time of 0.8 or 3.0 seconds. A suitable primary control is required for safe-start check and safety lockout.
- Power supply 220 Vac (+10, -15%), 50 Hz; 60 Hz (±10%)
- Modules used with the RM7800 Q7800A,B Universal Wiring Subbases. R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame
- Combustion air flow check Optional
- Dimensions (mm) 127 mm wide x 127 mm high x 133 mm deep with Q7800A module
- Genuine products
- Full CO/CQ
- VAT invoice
- Quote within 24 working hours
PRODUCT DESCRIPTION
Honeywell EC7823A1004 Burner Controller
Features:
- Factory-integrated system safety features.
- Flame detector relay only: a suitable primary control must be used for the safe-start check, safety lockout, load switching and the other functions a flame safeguard system requires.
- Supports a local or remote-mounted system information display.
- Plug-in flame signal amplifier module.
- Three LEDs show status information.
Specifications:
- Power supply: 220 Vac (+10, -15%), 50 Hz; 60 Hz (±10%)
- Modules used with the RM7800: Q7800A,B Universal Wiring Subbases. R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame
- Combustion air flow check: Optional
- Dimensions (mm): 127 mm wide x 127 mm high x 133 mm deep with Q7800A module
- 155 mm deep with Q7800B module
- Approvals: CSA: Certified, File No. LR95329-3.
- Operating temperature: -40 C to +60 C
Function and scope
According to Honeywell’s document (66-2031-3), the EC7823/RM7823 is a microprocessor-based flame detector relay that can be fitted with any 7800 SERIES amplifier to give relay action from one relay with two SPDT circuits when flame is present or not present. Functions include flame monitoring, system status indication, self-diagnostics and troubleshooting.
Honeywell states clearly that it is a flame detector relay only; a suitable primary control must be used to provide the safe-start check, safety lockout, load switching and other functions required in flame safeguard systems.
Compatibility and installation
- The system needs three parts: the EC7823 relay module, a Q7800 wiring subbase (Q7800A panel mount, Q7800B wall or burner mount) and a plug-in flame signal amplifier.
- The amplifiers and flame detectors (R7847, R7848, R7849, R7851, R7861, R7886…) are selected from Table 3 of the Honeywell document according to the detector (flame sensor) type.
- Options: Keyboard Display Module, PC interface, Data ControlBus module, remote display, first-out annunciator; maximum total connected load 2000 VA, 15 A fast-blow fuse.
Approvals and environment
- EC7823 version: Factory Mutual (report J.1.OYOA9.AF). RM7823 version (120 Vac): UL, CSA, Factory Mutual.
- Operating temperature -40°C to +60°C; storage -40°C to +66°C; humidity up to 85% RH non-condensing; vibration 0.5G.
- Honeywell lists the unit as SIL 3 capable.
Information to send for a quote
- The full code EC7823A1004 and the quantity; the supply voltage (EC = 220-240 Vac, RM = 120 Vac).
- The type of flame detector (ionization/flame rod, ultraviolet, infrared) so the matching amplifier and Q7800 subbase can be selected.
- The primary control in use, or to be replaced.
TECHNICAL SPECIFICATIONS
Specifications of Honeywell 7800 Series
| PARAMETER | VALUE |
|---|---|
| Model | EC7823A1004 |
| Power supply | 220 Vac (+10, -15%), 50 Hz; 60 Hz (±10%) |
| Modules used with the RM7800 | Q7800A,B Universal Wiring Subbases. R7847, R7848, R7849, R7851, R7852, R7861, or R7886 Flame |
| Combustion air flow check | Optional |
| Dimensions (mm) | 127 mm wide x 127 mm high x 133 mm deep with Q7800A module |
| Approvals | CSA: Certified, File No. LR95329-3. |
| Operating temperature | -40 C to +60 C |
| Brand | Honeywell |
| Origin | USA |
Specifications may vary with the ordered configuration. Contact a CAD engineer for sizing to your actual operating conditions.
FAQ
Frequently asked questions about CAD-TH-200
Does the EC7823 sequence the burner by itself?
No. Honeywell describes the EC7823/RM7823 as a flame detector relay; start-up sequence, safety lockout and load switching are handled by a primary control. If you need a complete burner control, talk to CAD to select the right model.
How do the EC7823 and RM7823 differ?
Mainly in supply voltage: the EC7823 uses 220-240 Vac and the RM7823 uses 120 Vac (both 50 or 60 Hz). The listed approvals also differ (RM7823 has UL, CSA, FM; the EC7823 has Factory Mutual per the document).
What accessories does the EC7823 need to operate?
A Q7800 wiring subbase (A panel mount or B wall/burner mount) and a plug-in flame signal amplifier, with a suitable flame detector; the amplifier determines the flame failure response time of 0.8 or 3.0 seconds.
What should I send CAD to quote an EC7823A1004?
Send the code EC7823A1004, quantity, the flame detector type in use and the system's primary control. CAD quotes within 24 working hours.