Honeywell Fire Sentry FS24X is a multi-spectrum triple IR flame detector (IR/IR/IR/Visible) that detects hydrocarbon and non-hydrocarbon fuel fires. Response 3-5 s to a 1 sq. ft. n-heptane fire at 30 m, 110° (FS24X-2) or 90° (FS24X-9, EN 54-10) field of view, 24 Vdc, IP66.

  • Response time 3-5 seconds for a 1 sq. ft. n-Heptane fire at 30 m; 3-10 seconds at 60 m
  • Spectral sensitivity Visible 400 – 700 nm; Near Band IR 0.7 – 1.1 µm; Wide Band IR 1.1 – 3.0 µm; Wide Band IR 3.0 – 5.0 µm
  • Operating voltage 24 Vdc nominal (18-32 Vdc), regulated
  • Operating humidity 5 to 98% relative humidity, non-condensing
REQUEST A QUOTE DOWNLOAD DATASHEET (PDF)
  • Genuine products
  • Full CO/CQ
  • VAT invoice
  • Quote within 24 working hours

PRODUCT DESCRIPTION

Honeywell FS24X Infrared Flame Detector

FS24X is the latest generation of high-tech multi-spectrum flame detector (IR / IR / IR / Visible). Using advanced WideBand IR™ and WideBand 4.3 micron IR™ detection technology that performs in all weather conditions, the FS24X is a quantum leap in flame detection. Its algorithms, multi-function software and dual microprocessors give the FS24X the highest fire detection performance combined with optimal false alarm immunity.

Technical details:

  • Detection time: 3-5 seconds for a 1 sq. ft. n-Heptane fire at 30 m; 3-10 seconds at 60 m
  • Sensor sensitivity: 400 – 700 nanometres Near Band IR: 0.7 – 1.1 microns Wide Band IR: 1.1 – 3.0 microns Wide Band IR: 3.0 – 5.0 microns
  • Communication: selectable RS-485 ModBus or RS-485 FireBus II
  • Other optional communication: HART (excluded under EN54-10)
  • Optional software interface providing graphics, real-time data and retrieval of stored information
  • Time and date stamping of events
  • Erasable, reprogrammable flash memory
  • Power requirement: 24 Vdc
  • Operating humidity: 5 to 98% relative humidity, non-condensing
  • Operating temperature:

110° field of view FS24X: -40ºC to +85ºC (-40ºF to +185ºF);

90° field of view FS24X: -60°C to +85°C (-76°F to +185°F)

Storage: -55ºC to +110ºC (-67ºF to +230ºF)

  • Three-color visual indicator: green for power, red for alarm, yellow for fault
  • 0 – 20 mA analog output, user-selectable source
  • Alarm, Fault and Fire output relays
  • Dual microprocessors for digital sampling and signal processing, data acquisition, communication and FirePic pre-fire event data storage
  • Two ¾” NPT or 25 mm conduit entries
  • Low power consumption
  • RFI and EMI immunity
  • Approvals: FM, cFM, IECEx, ATEX, CU-TR, EN54-10, Dash 5 and SIL 2
  • Ingress protection: IP66

Versions and configuration

  • FS24X-2: 110° field of view (±55° from the axis), operating temperature -40 to +85 °C.
  • FS24X-9: 90° field of view (±45°), operating temperature -60 to +85 °C; EN 54-10 certified (LPCB 1175a/02).
  • Switch-selectable sensitivity: very high (200 ft), high (150 ft), medium (100 ft) and low (50 ft) for the reference 1 sq. ft. n-heptane fire; response 3-5 s at 30 m and 3-10 s at 60 m.
  • Copper-free powder-coated aluminium or 316 stainless steel housing; IP66 and NEMA 4 & 4X; two M25 or 3/4 in. NPT conduit entries.

Outputs and communication

  • Relays: fire alarm (SPDT), fault (SPST) and auxiliary (SPDT), 1 A at 24 Vdc.
  • 0-20 mA analog output, source or sink selectable; green (power), red (alarm) and yellow (fault) LEDs.
  • Communication selectable between RS-485 Modbus and RS-485 FireBus II; optional HART module (not available on EN 54-10 units).
  • Power 56 mA operating, 106 mA in alarm at 24 Vdc (plus 155 mA when the heater is on, which switches on at about -17 °C).
  • FirePic stores pre-fire data and an event log with time stamps; PC software and the FSIM interface module for diagnostics; a swivel bracket is optional.

Applications and approvals

Applications named by the manufacturer: refineries and oil production facilities, off-shore platforms, turbine/compressor enclosures, oil and gas pipelines and pumping stations, LNG/LPG loading, natural gas/CNG plants, ethanol/methanol/IPA production and storage, crude oil and gasoline tank farms, aircraft hangars, paint and solvent storage, chemical facilities and power plants.

Approvals per the data sheet: FM (Class I Div. 1 & 2, Groups B, C, D and others), ATEX / IECEx (II 2 G Ex db IIC T4/T5/T6), CU-TR, INMETRO, EN 54-10 (FS24X-9), meets SIL 2 requirements (FMEDA available on request).

What to send for a quote

  • Field of view version (FS24X-2 or FS24X-9) and housing material (aluminium or 316 stainless steel).
  • Fuel type, and the distance and size of the fire to detect.
  • Conduit entry type (M25 or NPT) and swivel bracket.
  • Signal to the control panel: relay, 0-20 mA, Modbus or FireBus II.
  • Hazardous-area approvals required (FM, ATEX, IECEx, EN 54-10) and quantity.

CAD replies with a quote within 24 working hours of receiving the details.

TECHNICAL SPECIFICATIONS

Specifications of Honeywell FS24X

PARAMETER VALUE
Model FS24X
Response time 3-5 seconds for a 1 sq. ft. n-Heptane fire at 30 m; 3-10 seconds at 60 m
Spectral sensitivity Visible 400 – 700 nm; Near Band IR 0.7 – 1.1 µm; Wide Band IR 1.1 – 3.0 µm; Wide Band IR 3.0 – 5.0 µm
Operating voltage 24 Vdc nominal (18-32 Vdc), regulated
Operating humidity 5 to 98% relative humidity, non-condensing
Operating temperature (110° field of view) -40 °C to +85 °C (-40 °F to +185 °F)
Operating temperature (90° field of view) -60 °C to +85 °C (-76 °F to +185 °F)
Storage temperature -55 °C to +110 °C (-67 °F to +230 °F)
Three-color visual indicator green for power, red for alarm, yellow for fault
Certifications FM, IECEx, ATEX, CU-TR, INMETRO, EN54-10 (FS24X-9), SIL 2 capable
Ingress protection IP66 and NEMA 4 & 4X
Brand Honeywell
Field of view FS24X-2: 110°; FS24X-9: 90°
Analog output 0 - 20 mA, source or sink selectable
Housing material Copper-free powder-coated aluminum or 316 stainless steel

Specifications may vary with the ordered configuration. Contact a CAD engineer for sizing to your actual operating conditions.

FAQ

Frequently asked questions about CAD-SF-410

What is the difference between FS24X-2 and FS24X-9?

FS24X-2 has a 110° field of view and a -40 to +85 °C range. FS24X-9 has a 90° field of view, a -60 to +85 °C range and EN 54-10 certification.

How far can the FS24X detect a fire?

For the reference 1 sq. ft. n-heptane fire, the very high sensitivity setting detects up to about 200 ft (about 61 m); response is 3-5 s at 30 m and 3-10 s at 60 m. Lower sensitivity settings give shorter range.

Does the FS24X detect non-hydrocarbon fires?

Yes. The manufacturer states it detects hydrocarbon and non-hydrocarbon fuel fires in all environmental conditions.

How does the FS24X connect to a control system?

Fire, fault and auxiliary relays; a 0-20 mA output; RS-485 Modbus or FireBus II communication; HART is an optional module (not available on EN 54-10 units).

What do I need to send for an FS24X quote?

FS24X-2 or -9, housing material, fuel type and distance, output type and the approvals required. CAD replies within 24 working hours.

Used this product? Write a review

Your rating

20 to 1500 characters, no links.

CAD uses your name, company and text only to publish your review once approved. Your email is for CAD to check only; it is never shown or used for anything else.

MORE IN SAFETY SOLUTION

RELATED PRODUCTS

View the full equipment catalogue
Quote