Honeywell Sensepoint XCD RFD Flammable Gas Transmitter (Remote Sensor)
Sensepoint XCD RFD is a Honeywell 3-wire 4-20mA flammable gas transmitter for remotely mounted sensors up to 30 m away, range adjustable 0-100%LEL to 0-20%LEL, ATEX/IECEx, IP66.
- Brand Honeywell
- Series Sensepoint XCD
- Type Flammable gas transmitter, 3-wire 4-20mA, for remotely mounted flammable gas sensors (RFD = Remote Flammable Detector)
- Sensor distance Sensor can be mounted up to 30 metres (100 feet) from the transmitter; directly on the M25 entry at the bottom of the transmitter or remotely through suitable junction boxes or duct mounting assemblies
- Genuine products
- Full CO/CQ
- VAT invoice
- Quote within 24 working hours
PRODUCT DESCRIPTION
Honeywell Sensepoint XCD RFD Flammable Gas Transmitter (Remote Sensor)
Sensepoint XCD RFD (Remote Flammable Detector) is a Honeywell 3-wire 4-20mA flammable gas transmitter designed for remotely mounted flammable gas sensors. The sensor can be mounted up to 30 metres (100 feet) from the transmitter, including in areas up to 150°C (with the high temperature sensor) or hard to access, while the transmitter sits where it is easy to reach and read. It has a tri-colour LCD, 3 programmable relays, a gas range adjustable from 0-100%LEL down to 0-20%LEL, ATEX/IECEx approval and IP66.
It works with Sensepoint XCD remote flammable sensors (catalytic and infrared) or with the Sensepoint range of flammable gas detectors. This is the transmitter only: order the sensor separately.
How does Sensepoint XCD RFD differ from Sensepoint XCD and Sensepoint XCD RTD?
Sensepoint XCD RFD is the transmitter for remotely mounted flammable gas sensors, with a range adjustable from 0-100%LEL down to 0-20%LEL. Sensepoint XCD RTD is the transmitter for Sensepoint toxic and oxygen sensors (mounted directly or remotely). Sensepoint XCD (the detector version) is a transmitter with a flammable, toxic or oxygen sensor plugged into its base.
Sensepoint XCD RFD specifications
- Brand: Honeywell
- Series: Sensepoint XCD
- Type: Flammable gas transmitter, 3-wire 4-20mA, for remotely mounted flammable gas sensors (RFD = Remote Flammable Detector)
- Sensor distance: Sensor can be mounted up to 30 metres (100 feet) from the transmitter; directly on the M25 entry at the bottom of the transmitter or remotely through suitable junction boxes or duct mounting assemblies
- Gas range: User adjustable at the transmitter from 0-100%LEL down to 0-20%LEL; with the high temperature sensors (thermally matched beads) alarm set points as low as 5%LEL are possible
- Input voltage range: 18 to 32VDC (24VDC nominal)
- Max power consumption: 5 Watts
- Current output: Sink or source. ≥0.0<1.0mA: fault; 2.0mA or 4.0mA: inhibit (during configuration / user settings); 4.0mA to 20.0mA: normal gas measurement; 22.0mA: maximum over range
- Terminals: 18 x screw terminals suitable for wire diameter 0.5mm2 to 2.5mm2 (20AWG to 14AWG)
- Relays: 3 x 5A@250VAC; selectable normally open or normally closed (switch) and energised / de-energised (programmable). Alarm relays default normally open / de-energised; fault relay default normally open / energised
- Display: Tri-colour backlit LCD: steady green = normal, flashing yellow = fault, flashing red = alarm
- Configuration: Range, relay operation, alarm set points and electronic tag number adjusted using the LCD and non-intrusive magnetic switches; outputs automatically inhibited during adjustment
- Material: Transmitter housing: epoxy painted aluminium alloy LM25 or 316 stainless steel; Sensepoint XCD plug-in sensor and Sensepoint high temperature sensor: 316 stainless steel; Sensepoint standard sensor: PPS; weather protection: plastic
- Weight (approx): Aluminium alloy LM25: 2.0kg (4.4lbs); 316 stainless steel: 5.0kg (11lbs)
- Mounting: Integral mounting plate with 4 x mounting holes suitable for M8 bolts; surface mounting or horizontal / vertical pipe or structure 40.0-80.0mm (1.6 to 3.1 inches) in diameter, optional pipe mounting kit
- Entries: European ATEX/IECEx versions: 2 x M20 side entries and 1 x M25 bottom entry
- IP rating: IP66 in accordance with EN60529:1992
- Transmitter certified operating range: -40°C to +65°C (-40°F to +149°F); the display may become illegible below -20°C but the detector continues gas monitoring and recovers above -20°C
- Humidity / pressure / storage: Operating humidity continuous 20-90%RH (non-condensing), intermittent 0-99%RH; operating pressure 90-110kPa; storage -25°C to +65°C (-13°F to 131°F)
- Certification: European: ATEX Ex II 2 GD Ex d IIC Gb T6 (Ta -40°C to +65°C) Ex tb IIIC T85°C Db IP66; international: IEC Ex d IIC Gb T6 (Ta -40°C to +65°C) Ex tb IIIC T85°C Db IP66; China: GB Ex d IIC T4 GB3836.1&2 -2000, PA, CCCF; Korea: KTL Ex d IIC T6 (-40°C to +65°C); EMC: CE EN50270:2006, EN6100-6-4:2007
- Standard supply: Integral wall mounting plate, 2 x M20 side entries and 1 x M25 bottom entry, 1 x M20 plug, Allen key for locking screw, operating magnet, quick start guide and instruction manual CD; default settings, ranges and calibrations are 100% tested at the factory and each unit is supplied with a test certificate. Order the sensor separately
Compatible sensors
Per the datasheet the transmitter works with the sensors below (sensor performance; see the Sensepoint XCD RFD datasheet for the test conditions).
| Sensor | Selectable full scale range | Default range | Response time | Accuracy | Operating temperature | Default alarm A1 / A2 |
|---|---|---|---|---|---|---|
| Sensepoint standard temperature sensor (flammable 1 to 8) | 20 to 100%LEL | 100%LEL | < 25 secs (T90) | < ±1.5%LEL | -55°C to 80°C | 20%LEL / 40%LEL rising |
| Sensepoint high temperature sensor (flammable 1 to 8) | 20 to 100%LEL | 100%LEL | < 6 secs (T60), < 10 secs (T90) | < ±1.5%LEL | -55°C to 150°C | 20%LEL / 40%LEL rising |
| Plug-in Sensepoint XCD catalytic bead (flammable 1 to 8) | 20 to 100%LEL | 100%LEL | < 25 secs (T90) | < ±1.5%LEL | -40°C to 65°C | 20%LEL / 40%LEL rising |
| Plug-in Sensepoint XCD infrared: methane | 20 to 100%LEL | 100%LEL | < 30 secs (T90) | < ±1.5%LEL | -20°C to 50°C | 20%LEL / 40%LEL rising |
| Plug-in Sensepoint XCD infrared: propane (*) | 20 to 100%LEL | 100%LEL | < 30 secs (T90) | < ±1.5%LEL | -20°C to 50°C | 20%LEL / 40%LEL rising |
| Plug-in Sensepoint XCD infrared: carbon dioxide (*) | 2.00%Vol | 2.00%Vol | < 30 secs (T90) | < ±0.04%Vol | -20°C to 50°C | 0.40%V/V / 0.80%V/V rising |
(*) The datasheet says: contact Honeywell for availability.
Order codes
The transmitter and the sensor are ordered separately. In the CAD order-code table an M suffix means the Modbus version, ATEX/IECEx & AP codes use M20 entries and cCSAus codes use 3/4″NPT entries.
| Order code | Description |
|---|---|
| SPXCDALMRFD | ATEX, IECEx & AP approved SP XCD-RFD Remote Flammable (Cat or IR) Sensor input Transmitter with Painted Marine Grade Al, M20 Entry |
| SPXCDASMRFD | ATEX, IECEx & AP approved SP XCD-RFD Remote Flammable (Cat or IR) Sensor input Transmitter with 316SS, M20 Entry |
| SPXCDULNRFD | cCSAus approved SP XCD-RFD Remote Flammable (Cat or IR) Sensor input Transmitter with Painted Marine Grade Al,3/4NPT Entry |
| SPXCDUSNRFD | cCSAus approved SP XCD-RFD Remote Flammable (Cat or IR) Sensor input Transmitter with 316SS, 3/4NPT Entry |
| SPXCDALMRFDM | ATEX, IECEx & AP approved SP XCD-RFD Remote Flammable (Cat or IR) Sensor input Transmitter with Painted Marine Grade AL, M20 Entry, with MODBUS |
| SPXCDASMRFDM | ATEX, IECEx & AP approved SP XCD-RFD Remote Flammable (Cat or IR) Sensor input Transmitter with 316SS, M20 Entry, with MODBUS |
| SPXCDULNRFDM | cCSAus approved SP XCD-RFD Remote Flammable (Cat or IR) Sensor input Transmitter with Painted Marine Grade Al, 3/4NPT Entry, with MODBUS |
| SPXCDUSNRFDM | cCSAus approved SP XCD-RFD Remote Flammable (Cat or IR) Sensor input Transmitter with 316SS, 3/4NPT Entry, with MODBUS |
| SPXCDXSRFXSS | Flammable CAT 0-100%LEL (20,0 to 100.0%LEL, 10%LEL) Sensor Cartridge with Socket Housing |
| SPXCDXSRRXSS | Methane IR 0-100%LEL (20,0 to 100.0%LEL, 10%LEL) Sensor Cartridge with Socket Housing |
| SPXCDXSRPXSS | Propane IR 0-100%LEL (20,0 to 100.0%LEL, 10%LEL) Sensor Cartridge with Socket Housing |
| SPXCDXSRB1SS | Carbon Dioxide IR 0-2.00%VOL only with Socket Housing Sensor Cartridge with Socket Housing |
| SPXCDXSRB2SS | Carbon Dioxide IR 0-5.00%VOL only with Socket Housing Sensor Cartridge with Socket Housing |
| SPXCDXSFXSS | Flammable CAT 0-100%LEL (20 to 100%LEL, 10%LEL) |
| SPXCDXSRXSS | Methane IR 0-100%LEL (20 to 100%LEL, 10%LEL) |
| SPXCDXSPXSS | Propane IR 0-100%LEL (20 to 100%LEL, 10%LEL) |
| SPXCDXSB1SS | Carbon Dioxide IR 0-2.00% v/v only |
Applications
The datasheet lists: in and around gas turbine enclosures and solvent based printing and coating drying ovens (with high temperature sensors); compliance with the requirements of HSE guidance note PM84; the transmitter can be mounted in an easy-to-access area even if the sensor is in a hard-to-access or restricted-access area.
TECHNICAL SPECIFICATIONS
Specifications of Honeywell Sensepoint XCD RFD Flammable Gas Transmitter (Remote Sensor)
| PARAMETER | VALUE |
|---|---|
| Model | Sensepoint XCD RFD |
| Brand | Honeywell |
| Series | Sensepoint XCD |
| Type | Flammable gas transmitter, 3-wire 4-20mA, for remotely mounted flammable gas sensors (RFD = Remote Flammable Detector) |
| Sensor distance | Sensor can be mounted up to 30 metres (100 feet) from the transmitter; directly on the M25 entry at the bottom of the transmitter or remotely through suitable junction boxes or duct mounting assemblies |
| Gas range | User adjustable at the transmitter from 0-100%LEL down to 0-20%LEL; with the high temperature sensors (thermally matched beads) alarm set points as low as 5%LEL are possible |
| Input voltage range | 18 to 32VDC (24VDC nominal) |
| Max power consumption | 5 Watts |
| Current output | Sink or source. ≥0.0<1.0mA: fault; 2.0mA or 4.0mA: inhibit (during configuration / user settings); 4.0mA to 20.0mA: normal gas measurement; 22.0mA: maximum over range |
| Terminals | 18 x screw terminals suitable for wire diameter 0.5mm2 to 2.5mm2 (20AWG to 14AWG) |
| Relays | 3 x 5A@250VAC; selectable normally open or normally closed (switch) and energised / de-energised (programmable). Alarm relays default normally open / de-energised; fault relay default normally open / energised |
| Display | Tri-colour backlit LCD: steady green = normal, flashing yellow = fault, flashing red = alarm |
| Configuration | Range, relay operation, alarm set points and electronic tag number adjusted using the LCD and non-intrusive magnetic switches; outputs automatically inhibited during adjustment |
| Material | Transmitter housing: epoxy painted aluminium alloy LM25 or 316 stainless steel; Sensepoint XCD plug-in sensor and Sensepoint high temperature sensor: 316 stainless steel; Sensepoint standard sensor: PPS; weather protection: plastic |
| Weight (approx) | Aluminium alloy LM25: 2.0kg (4.4lbs); 316 stainless steel: 5.0kg (11lbs) |
| Mounting | Integral mounting plate with 4 x mounting holes suitable for M8 bolts; surface mounting or horizontal / vertical pipe or structure 40.0-80.0mm (1.6 to 3.1 inches) in diameter, optional pipe mounting kit |
| Entries | European ATEX/IECEx versions: 2 x M20 side entries and 1 x M25 bottom entry |
| IP rating | IP66 in accordance with EN60529:1992 |
| Transmitter certified operating range | -40°C to +65°C (-40°F to +149°F); the display may become illegible below -20°C but the detector continues gas monitoring and recovers above -20°C |
| Humidity / pressure / storage | Operating humidity continuous 20-90%RH (non-condensing), intermittent 0-99%RH; operating pressure 90-110kPa; storage -25°C to +65°C (-13°F to 131°F) |
| Certification | European: ATEX Ex II 2 GD Ex d IIC Gb T6 (Ta -40°C to +65°C) Ex tb IIIC T85°C Db IP66; international: IEC Ex d IIC Gb T6 (Ta -40°C to +65°C) Ex tb IIIC T85°C Db IP66; China: GB Ex d IIC T4 GB3836.1&2 -2000, PA, CCCF; Korea: KTL Ex d IIC T6 (-40°C to +65°C); EMC: CE EN50270:2006, EN6100-6-4:2007 |
| Standard supply | Integral wall mounting plate, 2 x M20 side entries and 1 x M25 bottom entry, 1 x M20 plug, Allen key for locking screw, operating magnet, quick start guide and instruction manual CD; default settings, ranges and calibrations are 100% tested at the factory and each unit is supplied with a test certificate. Order the sensor separately |
Specifications may vary with the ordered configuration. Contact a CAD engineer for sizing to your actual operating conditions.
OTHER CODES IN THE RANGE
Same series
- Sensepoint XCD Honeywell Sensepoint XCD Fixed Gas Detector (Flammable, Toxic, Oxygen)
- SPXCDALMFX Honeywell Sensepoint XCD SPXCDALMFX Fixed Gas Detector (Flammable, Catalytic)
- SPXCDALMG1 Honeywell Sensepoint XCD SPXCDALMG1 Fixed Gas Detector (Hydrogen)
- SPXCDALMO1 Honeywell Sensepoint XCD SPXCDALMO1 Fixed Gas Detector (Oxygen)
- SPXCDALMRX Honeywell Sensepoint XCD SPXCDALMRX Fixed Gas Detector (Methane, Infrared)
FAQ
Frequently asked questions about Sensepoint XCD RFD
How does Sensepoint XCD RFD differ from Sensepoint XCD and Sensepoint XCD RTD?
Sensepoint XCD RFD is the transmitter for remotely mounted flammable gas sensors, with a range adjustable from 0-100%LEL down to 0-20%LEL. Sensepoint XCD RTD is the transmitter for Sensepoint toxic and oxygen sensors. Sensepoint XCD is the detector version with a sensor plugged into the base of the transmitter.
How far from the transmitter can the sensor be mounted?
The sensor can be mounted up to 30 metres (100 feet) from the transmitter; the high temperature sensor operates up to 150°C (302°F).
What approvals and protection rating does Sensepoint XCD RFD have?
ATEX Ex II 2 GD Ex d IIC Gb T6 (Ta -40°C to +65°C) Ex tb IIIC T85°C Db IP66, IEC Ex d IIC Gb T6; IP66 rating; 18 to 32VDC supply, 5W max.