Honeywell Minipeeper C7035A1080 UV Flame Detector
The ultraviolet flame detector senses ultraviolet radiation emitted by a burning flame. The detectors are used with Honeywell flame safeguard controls to provide flame supervision for gas, oil or combination gas-oil burners.
- Flame detection End viewing
- Operating temperature rating 0 °F to 250 °F (-18 °C to +121 °C), or -40 °F to 250 °F (-40 °C to +121 °C), depending on model
- Maximum pressure rating 5 psi (34.5 kPa)
- Mounting Collar with 1-11-1/2 NPSM internal threads for mounting on a 1-inch sight pipe. (DIN-approved C7035A1064 has 1-11 BSP.P1 threads.)
PRODUCT DESCRIPTION
Honeywell Minipeeper C7035A1080 UV Flame Detector
Features:
- The flame detector is used with RA890G devices or R7249A, R7290A, R7749B and R7849A, B amplifiers and the appropriate Honeywell controls.
- The C7035A has an integral threaded collar (1-11-1 / 2 NPSM internal) for mounting on a 1-inch sight pipe.
- The C7035A housing meets Underwriters Laboratories Inc. requirements for raintight construction and complies with NEMA enclosure standards, types 4 and 4X.
- When properly installed, it is rated for 5 psi pressure.
- The C7035A ultraviolet sensing tube is field-replaceable.
- Flame detectors can be wired in parallel for installations where the flame is hard to sight.
Specifications:
- Flame detection: End viewing.
- Operating temperature rating: 0 ° F to 250 ° F (-18 ° C to + 121 ° C), or -40 ° F to 250 ° F (-40°C to + 121 ° C), depending on model.
- Maximum pressure rating: 5 psi (34.5 kPa).
- Mounting: Collar with 1-11-1 / 2 NPSM internal threads for mounting on a 1-inch sight pipe. (DIN-approved C7035A1064 has 1-11 BSP.P1 threads.)
- Wiring connections: Two 6 ft. (1.83 m), color-coded
- 18 AWG silicone rubber insulated leadwires, NEC Class 1, rated at 302 ° F (150°C).
- The back of the detector has 1 / 2-14 NPSM internal threads for conduit connection. The C7035A1080 has 10-foot (3-meter) leadwires rated at 600°F (316°C).
TECHNICAL SPECIFICATIONS
Specifications of Honeywell Minipeeper
| PARAMETER | VALUE |
|---|---|
| Model | C7035A1080 |
| Flame detection | End viewing |
| Operating temperature rating | 0 °F to 250 °F (-18 °C to +121 °C), or -40 °F to 250 °F (-40 °C to +121 °C), depending on model |
| Maximum pressure rating | 5 psi (34.5 kPa) |
| Mounting | Collar with 1-11-1/2 NPSM internal threads for mounting on a 1-inch sight pipe. (DIN-approved C7035A1064 has 1-11 BSP.P1 threads.) |
| Wiring connections | Two color-coded 18 AWG NEC Class 1 leadwires, silicone rubber insulated; C7035A1080 10 feet (3 meters) long, rated 600 °F (316 °C) |
| Used with | RA890G or R7249A, R7290A, R7749B, R7849A,B amplifiers |
| Enclosure rating | Meets NEMA types 4 and 4X, raintight per UL |
| Conduit connection | 1/2-14 NPSM internal threads on the back of the detector |
| Approvals | UL listed File No. MP268; CSA certified Master Report LR 95329-1; Factory Mutual approved |
| Brand | Honeywell |
Specifications may vary with the ordered configuration. Contact a CAD engineer for sizing to your actual operating conditions.